4. Fire overpressure
Buildings or communities must have a pressurized water network for fire-fighting, and full automation of the system is generally required.
In other words, the circuit needs to be under constant pressure, so that simply opening a lance provides the necessary pressure and flow.
The general rules governing fire systems are briefly described at the beginning of this article.
For high-rise buildings, the water reserve must be a minimum of 120 m3, and this reserve must be maintained while the tank is being cleaned. In practice, this means 2 tanks of 120 m3, 3 tanks of 60 m3 or 4 tanks of 40 m3.
The booster pump must be capable of delivering a flow rate of 120 m3 / h, corresponding to the simultaneous flow rate of 2 wet columns (NF S 61-751), and must systematically include an emergency pump.
The network is supplied,...