The first article, “Traditionally Installed Glazing: Determining
Thicknesses” ( [N 4 405] ), addressed glazing installed in frames with glazing beads
that meet the requirements of standard NF DTU No. 39, or glazing consisting
of a single unit of tempered glass.
This article specifically addresses glazing when it is bonded
to a substrate (VEC – bonded exterior glazing) or point-fixed to a
structure (VEA – bolted exterior glazing).
The rules applicable to these glazing systems are taken from CSTB
technical reports No. 3488 for VEC and No. 3574 for VEA, which
define, on the one hand, the loads that must be taken into account
and, on the other hand, the criteria that must be met depending on
the installation technique.
The mechanical performance of glazing depends on the nature of
its basic components, the way these components are assembled in the
final glazing unit, and the load exerted on the glazing during installation.
We will therefore focus on specifying the loads acting on glazing
systems based on their installation type, and then provide the calculation
formulas used to determine their thickness.
Calculation examples are provided to illustrate the process for
determining the correct composition of a glazing unit.