3. Tests to determine the mobilizable heat of combustion
In order to determine the mobilizable heat of combustion, the following sequence must be carried out:
Measurement of the gross calorific value PCS1 (MJ/kg) of the material concerned. The density of the material ρ1 in kg/m3 is supplied by the test applicant.
Carrying out a test according to the standardized thermal program for 1/2 h, on a specimen of dimensions 0.30 × 0.40 (m) and thickness e0 (m). This thickness e0 is determined by the laboratory on the applicant's proposal. It takes into account the nature of the material and the different thicknesses used. It is chosen so that the residual thickness e3 is at least 5 mm, or so that the formula in point 4 can be applied.
After 1/2 h exposure, extinguish rapidly with CO2 and cool the test tube.
...