3. Supercharging Technologies and Semi-Flooded Operation
Advances in transcritical architectures have led to the development of systems that utilize evaporator supercharging. This strategy takes advantage of the fact that increasing the evaporation temperature of the positive-pressure units reduces the power consumption of the MT compressors. A 5 °C increase in the BP can thus generate up to 15% in annual energy savings.
The so-called “semi-submerged” operating mode involves maintaining a very low superheat (close to 1 K). This increases the heat transfer coefficient at the outlet of the heat exchangers (Figure13).
You do not have access to this resource.
Exclusive to subscribers. 97% yet to be discovered!
Already subscribed?
Log in!
Ongoing reading
Supercharging Technologies and Semi-Flooded Operation
Bibliography
-
MEUNIER (F.), RIVET (P.), TERRIER (M.-F.) - Froid industriel. - 2e édition, Dunod (2010).
-
DESMONS (J.) - Aide-mémoire froid industriel. - 2e édition, Dunod (2023).
Regulations
Regulation (EU) 2024/573 of the European Parliament and of the Council of February 7, 2024, on fluorinated greenhouse gases, amending Directive (EU) 2019/1937 and repealing Regulation (EU) No. 517/2014. Published in the Official Journal of the European Union, Series L, No. 31, February 20, 2024. Text of relevance to the EEA (European Economic Area).
Directory
Manufacturers – Suppliers – Distributors (non-exhaustive list)
Suppliers of heat exchangers and refrigeration equipment:
https://www.luvegroup.com/
https://hk-refrigeration.grouplfb.com/fr/
https://guntner.com/fr-fr
...