System-specific provisions
Fire safety in high-rise buildings (IGH) - Technical instruction on smoke control

Add to my library

TBA3055 V1 Article

System-specific provisions
Fire safety in high-rise buildings (IGH) - Technical instruction on smoke control

Authors :

Review date: April 29, 2021 | Lire en français

Add to my library Add to my library

Logo Techniques de l'Ingenieur You do not have access to this resource.
Request your free trial access! Free trial

Already subscribed?

4. System-specific provisions

4.1 Solution A

Air inlets for intercommunication devices have their upper edge no more than 1 m above the floor.

Smoke extraction outlets on intercommunication devices have their bottom part at least 1.80 m above the floor and are located entirely in the upper third of the device.

The air supply and smoke extraction vents of intercommunication devices are fitted with flame-retardant shutters rated at 1 h or E 60, closed in the standby position.

The air supply and smoke extraction flow rates in intercommunication devices are at least 0.20 m 3 /s/m 2 . As intercommunication devices must always be overpressurized in relation...