3. AEV tests
The performance of curtain walls must be verified using a mock-up
on a test bench. NF EN 13-830 (product standard) and DTU 33.1 (May
2008) define the rules and criteria for testing. Tests are carried
out in accordance with standards NF EN 12 152 – 12 153 – 12 154 –
12 178 published in 2000 and 2002:
air: 5 classes ;
water: watertight up to normal pressure ;
Normal wind: deflection at 1/200 limited to 15 mm ;
Extreme wind: extreme pressure = as per DTU.
To carry out a test, it is necessary
to build a model representative of the proposed design or site. The
height can be limited to the height of the floor (distance between
2 common supports), since it is then possible...