This article outlines the basic principles of analog frequency correction.
Calculating a frequency-domain control system involves working from the gain and phase curves of the open-loop transfer function (assembly: actuator – process – sensor) and striving to obtain a satisfactory shape for the closed-loop frequency response.
Based on the frequency response of a well-tuned second-order servo (damping z = 0.43, corresponding to a resonance factor Q = 2.3 dB), we aim to create a closed-loop corrector that will give a flat frequency characteristic from low frequencies onwards, with a resonance factor of around 2.3 dB, before dropping off towards high frequencies.
Using the approximate equivalences between the time and frequency properties of a servo system (see General principles of correction
, in this Automatic section), we translate frequency specifications into temporal terms and vice versa.
The transition from open-loop frequency response,
, to closed-loop frequency response,
, uses Black's abacus (see Frequency Study of Continuous Systems).
, in this section Automatic).