8. Civil engineering of structures
-
Accessibility of structures
All the parts of a collective pipe, the premises or specialized locations (common section, columns, collective branches, service connection communication circuits, metering premises) must be installed in common locations in conditions such that the DSO's agents can have permanent access to the installations and carry out their work and checks properly.
-
Location of main circuit breaker
The individual or collective main circuit breaker (CCPI or CCPC) is placed on a vertical wall accessible from the public domain, without the need for controlled access. This requirement applies to underground connections and, in accordance with paragraph 551.1.2 of standard NF C 15-100, to producer connections coming from outside buildings. In the case of a...