6. Our advice
In the case presented below, we consider on the one hand the dreaded event Gas leak on a pipeline with a frequency of occurrence of 10 -2 /year, and on the other hand a Safety Instrumented System (SIS) composed of :
a gas detector with a PFD equal to 10 -1 /sollicitation;
a treatment plant with a PFD equal to 10 -2 /sollicitation;
an automatic isolation valve with a PFD equal to 10 -1 /sollicitation.
Based on the above data, the PFD of the SIS is evaluated as follows:
PFD (SIS) = PFD (Gas detector) + PFD (Logic processing) + PFD (Isolation valve) = 10 -1...