Mistakes to avoid
SIL level assessment of Safety Instrumented Functions (SIF) – Essential concepts
Practical sheet REF: FIC0540 V1
Mistakes to avoid
SIL level assessment of Safety Instrumented Functions (SIF) – Essential concepts

Author : Olivier IDDIR

Publication date: July 10, 2014, Review date: November 13, 2016 | Lire en français

Logo Techniques de l'Ingenieur You do not have access to this resource.
Request your free trial access! Free trial

Already subscribed?

5. Mistakes to avoid

5.1 Do not allocate SIL levels to barriers that are not instrumented.

The notion of SIL is only applicable to instrumented barriers (covered by IEC 61508 and IEC 61511 standards). It makes no sense to say that a non-return valve is SIL 1. For all non-instrumented barriers, it is preferable to refer to the notion of Confidence Level introduced by INERIS in the OMEGA 10 guide.