9. Typical malfunctions
9.1 Incorrect zero-sequence settings on current-operated protection devices
When the underground network expands and we "forget" to take into account the new value of the capacitive current of the feeder to be protected, the condition I setting > 1.2 × 3Ic may no longer be met.
The protection opens its circuit-breaker unexpectedly when a low-resistance earth fault occurs on a neighbouring feeder: the term "sympathy" tripping...