5. High-voltage generators

5.1 Test generator

When it comes to high-voltage generators, there are a number of special features that need to be borne in mind.

  • It must be able to operate at a very wide range of voltages: from a few kilovolts (50 kV) to 1,000 or 1,500 kV rms, possibly by modifying the transformation ratio with a series-parallel winding in the low-voltage winding.

  • High-voltage generators are generally used intermittently, and their operating time, particularly for dielectric tests, is very short (at generator limit voltages, operating time is generally limited to 1 or 2 min, or even 5 min, plus the time required for voltage rise and fall). As a result, the device will be required to deliver...

You do not have access to this resource.
Logo Techniques de l'Ingenieur

Exclusive to subscribers. 97% yet to be discovered!

You do not have access to this resource. Click here to request your free trial access!

Already subscribed?


Ongoing reading
High-voltage generators

Article included in this offer

"Electronic measurements and tests"

( 80 articles )

Complete knowledge base

Updated and enriched with articles validated by our scientific committees

Services

A set of exclusive tools to complement the resources

View offer details

Contenus associés

Sur le même sujet

Veille personnalisée : Inscrivez-vous !

Dans les ressources documentaires

Puissance en courant continu et en courant alternatif

Cet article détaille le principe et les méthodes de mesure des puissances électriques, en courant continu...

Appareils de contrôle de la sécurité électrique

Avant de présenter les différents appareils de contrôle pouvant assurer la sécurité électrique, cet artic...

Méthodes de zéro en courant continu

Basés sur la méthode d’opposition (ou de zéro , ou d’équilibre ), les procédés qui vont être décrits...

Méthodes de zéro en courant alternatif

Les méthodes de zéro sont couramment utilisées en métrologie. Elles permettent de comparer soit directeme...

Tous les livres blancs
Article Redéfinir la seconde
18 September 2014
Redéfinir la seconde

L’utilisation d’une architecture fibrée améliore la définition de l’unité de temps, la seconde.

Toutes les actualités
Contact us